Description
A vulnerability has been identified in SIMATIC Drive Controller family (All versions < V2.9.2), SIMATIC Drive Controller family (All versions >= V2.9.2 < V2.9.4), SIMATIC ET 200SP Open Controller CPU 1515SP PC (incl. SIPLUS variants) (All versions), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants) (All versions < V21.9), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants) (All versions >= V21.9 < V21.9.4), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 Ready4Linux (All versions), SIMATIC S7-1200 CPU family (incl. SIPLUS variants) (All versions < V4.5.0), SIMATIC S7-1200 CPU family (incl. SIPLUS variants) (All versions >= V4.5.0 < V4.5.2), SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions < V2.9.2), SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions >= V2.9.2 < V2.9.4), SIMATIC S7-1500 Software Controller (All versions < V21.9), SIMATIC S7-1500 Software Controller (All versions >= V21.9 < V21.9.4), SIMATIC S7-PLCSIM Advanced (All versions < V4.0), SIMATIC S7-PLCSIM Advanced (All versions >= V4.0 < V4.0 SP1), SIPLUS TIM 1531 IRC (All versions < V2.3.6), TIM 1531 IRC (All versions < V2.3.6). An unauthenticated attacker could cause a denial-of-service condition in a PLC when sending specially prepared packet over port 102/tcp. A restart of the affected device is needed to restore normal operations.
CVSS breakdown
Affected products
- Siemens / SIMATIC Drive Controller familyAll versions < V2.9.2 – All versions < V2.9.2
- Siemens / SIMATIC Drive Controller familyAll versions >= V2.9.2 < V2.9.4 – All versions >= V2.9.2 < V2.9.4
- Siemens / SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants)All versions >= V21.9 < V21.9.4 – All versions >= V21.9 < V21.9.4
- Siemens / SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants)All versions < V21.9 – All versions < V21.9
- Siemens / SIMATIC ET 200SP Open Controller CPU 1515SP PC2 Ready4LinuxAll versions – All versions
- Siemens / SIMATIC ET 200SP Open Controller CPU 1515SP PC (incl. SIPLUS variants)All versions – All versions
- Siemens / SIMATIC S7-1200 CPU family (incl. SIPLUS variants)All versions < V4.5.0 – All versions < V4.5.0
- Siemens / SIMATIC S7-1200 CPU family (incl. SIPLUS variants)All versions >= V4.5.0 < V4.5.2 – All versions >= V4.5.0 < V4.5.2
- Siemens / SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants)All versions < V2.9.2 – All versions < V2.9.2
- Siemens / SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants)All versions >= V2.9.2 < V2.9.4 – All versions >= V2.9.2 < V2.9.4
- Siemens / SIMATIC S7-1500 Software ControllerAll versions < V21.9 – All versions < V21.9
- Siemens / SIMATIC S7-1500 Software ControllerAll versions >= V21.9 < V21.9.4 – All versions >= V21.9 < V21.9.4
- Siemens / SIMATIC S7-PLCSIM AdvancedAll versions < V4.0 – All versions < V4.0
- Siemens / SIMATIC S7-PLCSIM AdvancedAll versions >= V4.0 < V4.0 SP1 – All versions >= V4.0 < V4.0 SP1
- Siemens / SIPLUS TIM 1531 IRCAll versions < V2.3.6 – All versions < V2.3.6
- Siemens / TIM 1531 IRCAll versions < V2.3.6 – All versions < V2.3.6